Post time: 2021-05-29 Browse: 715
| Serial number | Transformer capacity( kva) | High side current (A) | High voltage side fuse type (A) | Low side current(A) | Low-voltage side fuse type(A) |
| 1 | 5 | 0.29 | 3 | 7.22 | 10 |
| 2 | 10 | 0.58 | 3 | 14.43 | 20 |
| 3 | 20 | 1.15 | 3 | 28.87 | 30 |
| 4 | 30 | 1.73 | 5 | 43.30 | 50 |
| 5 | 50 | 2.89 | 10 | 72.17 | 75 |
| 6 | 80 | 4.62 | 10 | 115.47 | 150 |
| 7 | 100 | 5.77 | 15 | 144.34 | 150 |
| 8 | 125 | 7.22 | 15 | 180.43 | 200 |
| 9 | 160 | 9.24 | 20 | 230.95Z | 250 |
| 10 | 200 | 11.55 | 20 | 288.68 | 300 |
| 11 | 250 | 14.43 | 25 | 360.85 | 400 |
| 12 | 315 | 18.19 | 30 | 454.68 | 500 |
| 13 | 400 | 23.09 | 40 | 577.37 | 600 |
| 14 | 500 | 28.87 | 50 | 721.71 | 750 |
High side fuse selection: 1. If the capacity is below 100KVA, the high-voltage side should be selected according to 2-3 times the rated current of the transformer. 2. For those with a capacity of 100KVA or more, the high-voltage side fuse should be selected according to 1.5-2 times the rated current of the transformer. ■Low-voltage side fuse selection The low-voltage side fuse of the transformer is selected according to the rated current of the transformer. | |||||