Serial numberTransformer capacity( kva)High side current (A)High voltage side fuse type (A)Low side current(A)Low-voltage side fuse type(A)
150.2937.2210
2100.58314.4320
3201.15328.8730
4301.73543.3050
5502.891072.1775
6804.6210115.47150
71005.7715144.34150
81257.2215180.43200
91609.2420230.95Z250
1020011.5520288.68300
1125014.4325360.85400
1231518.1930454.68500
1340023.0940577.37600
1450028.8750721.71750

  High side fuse selection:

 1. If the capacity is below 100KVA, the high-voltage side should be selected according to 2-3 times the rated current of the transformer.

 2. For those with a capacity of 100KVA or more, the high-voltage side fuse should be selected according to 1.5-2 times the rated current of the transformer.

  ■Low-voltage side fuse selection The low-voltage side fuse of the transformer is selected according to the rated current of the transformer.